Fuel spray fire – Déjà vu: Prepare and prevent it from happening to you!

  • Safety Flash
  • Published on 27 June 2017
  • Generated on 5 May 2025
  • IMCA SF 16/17
  • 2 minute read

The United States Coast Guard (USCG) has published Marine Safety Alert 06-17 to bring attention to ‘yet another fuel spray fire’. The USCG notes that “these types of incidents, involving fuel leakages contacting hot surfaces and igniting, happen too frequently and have been a focus of various marine safety organizations such as the IMO for many years.”

What happened

On a 194 GRT offshore supply vessel with an unmanned engine room, a main engine low fuel pressure alarm occurred on the bridge, and was investigated by the crew.

The crew member on watch entered the engine room and identified a high-pressure fuel leak spraying over and upon the port engine’s turbocharger. He also reported a large quantity of diesel fuel in the bilge.

The Master then went down into the engine room and witnessed the ignition of the fire. Using a hand held portable fire extinguisher he quickly attempted to extinguish the fire without success.

The Master activated the general alarm, secured the hatches, had crew members secure the ventilation dampers and closed the remote fuel shut-off valves to the engine room. The fire then quickly self-extinguished. No-one was harmed, but this engine room fire led to significant damage, operational down-time of the vessel, and lost company revenues.

the crew member spotted fuel spraying from ruptured hose onto the port engine's turbocharger
the fire led to significant damage, operational down-time of the vessel and lost company revenues

What went wrong? What were the causes?

The source of the fuel leak was identified to be a rupture on a flexible fuel hose connected to the fuel filter assembly.

Lessons learned

The USCG recommendations can be summarised thus:

  • Avoid an “out of sight, out of mind mentality” and regularly inspect unmanned machinery spaces.

  • Inspect fuel and lubricating systems closely from source tanks to system end points.

  • Examine all heat sources particularly with respect to engine exhausts.

  • Minimise the use of non-metallic flexible hoses in systems carrying flammable liquids particularly around engine areas where failures leading to leakage or spray may find hot spots capable of igniting the fluids.

Please refer to the fuller report and recommendations on the USCG website.

Latest Safety Flashes:

BSEE: Nitrogen Cylinder Rupture Causing Worker Injuries and Equipment Damage

The United States Bureau of Safety and Environmental Enforcement (BSEE) has published Safety Alert 494 relating to a Nitrogen Cylinder rupture which caused injuries and equipment damage.

Read more
Person fractured foot during elevator inspection
Read more
Detergent chemical burn

Leaked detergent resulted in slight chemical burns onboard a vessel.

Read more
Positive findings and good practices

A member highlights some examples of positive findings and good practices on board some of their vessels.

Read more
Hydrogen Sulphide (H2S) detected onboard vessel

Several persons reported to bridge about a smell of septic or rotten eggs that was present all over the vessel. Hydrogen Sulphide (H2S) was suspected.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.