UK HSE: Motion Compensated Gangways Auto-Retraction

  • Safety Flash
  • Published on 19 August 2025
  • Generated on 28 August 2025
  • IMCA SF 15/25
  • 4 minute read

The UK Health and Safety Executive (HSE) has published Safety Notice ED03-2025 relating to power failure or control system error can cause the unplanned retraction of motion compensated gangways (MCGs) posing a serious risk to operators and users of a gangway.

Target audience for the UK HSE Safety Notice ED03-2025 is Offshore Installation duty holders and vessel owners / operators of offshore vessels, windfarm operators, principal contractors and contractors.

Outline of the problem

There continues to be incidents where failure or error of a motion compensated gangway (MCG) power or control system has resulted in the gangway retracting without warning to the operator or persons crossing the gangway.

Unplanned retraction, also known as auto-retraction, poses a significant, foreseeable risk to personnel on the gangway if they are not given adequate warning to allow them to move to a safe location or brace for sudden movement, or allow sufficient time for the gangway operator to override the retraction.

Lack of warning that the gangway is about to retract can lead to people:

falling onto the gangway
being struck by moving parts
falling from height resulting in serious injury or death.

A warning, by definition, is advanced notice that a potentially dangerous event is about to occur. The purpose of the warning is to enable persons to make themselves safe before the event occurs. Audible and/or visual alarms that are triggered at the same time the gangway retracts are not considered to provide adequate warning.

This issue was highlighted in HSE Safety Notice ED02-2024 Risk of serious injury from motion compensated gangways, which states:

Operators, duty holders and vessel owners or operators should ensure that any gangway auto-retraction function provides suitable audible and visible warnings which allow users sufficient time to make themselves safe before the auto-retraction function activates.

Since the publication of ED02-2024, the output and conclusions of a good practice workshop conducted by G+/IMCA in partnership with Energy Institute has been published. It states Walk-to-Work (W2W) providers should provide an [auto] disconnect response that does not endanger the gangway user, with sufficient warnings and time.

DNV, as part of a joint industry project, produced industry guidance “Gangway Access to Offshore Facilities – Walk-to-Work” (PP097552 – Rev 1) states: there should be sufficient alarms (visual and/or audible) installed to inform the gangway personnel and personnel crossing the gangway, of the current status of the gangway system and to warn of imminent action, such as disconnection.

Despite the safety notice ED02-2024, and the publication of industry good practice, UK HSE has become aware that gangways that provide insufficient warning before auto-retraction are still being used in the offshore oil and gas and renewables industry.

Action required

Oil and gas and renewable energy duty holders must review their gangway arrangements to identify any gangways that do not provide sufficient warning prior to auto-retraction. If it is found that the gangway can retract without sufficient warning the gangway should not be used until suitable controls and additional risk reduction measures are in place.

Duty holders must review their gangway design, including the testing that has been carried out of all automatic functions. Duty holders should carry out a suitable and sufficient technical risk assessment to understand all operational states of the control system under which the gangway may auto-retract, including that the control system will only result in auto-retraction if personnel are not at risk.

Use of gangway operators to override auto-retractions should be rigorously risk assessed.

Although Safety Notice ED03-2025 only applies to the jurisdiction of the UK, IMCA supports and strongly recommends similar actions are taken wherever motion compensated gangways are deployed worldwide.

Latest Safety Flashes:

UK HSE: Motion Compensated Gangways Auto-Retraction

The UK Health and Safety Executive (HSE) has published Safety Notice ED03-2025

Read more
Brazil: diver permanently disabled after decompression illness

Conviction of diving company upheld as work accident suffered by a diver who lost strength in his upper limbs and the ability to move, requiring permanent use of a wheelchair.

Read more
Diver reports unwell post-dive: non-decompression illness

A diver experienced a dizzy spell about one hour after completing a diving operation

Read more
Shore-side crane boom collides with vessel mast

During shipyard lifting operations, the boom of a dock crane made contact with the vessel mast.

Read more
Injury sustained while operating steel lifting magnet

While preparing to transfer steel plates using a steel lifting magnet, a crew person was injured.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.