Regulator fire

  • Safety Flash
  • Published on 2 September 2003
  • Generated on 22 February 2025
  • IMCA SF 12/03
  • 2 minute read

This incident was originally included in safety flash 11/03, but the flash is being reissued in the light of additional feedback on the recommendations previously given. The earlier version has been removed from safety flash 11/03.

What happened?

A member has recently experienced two oxygen regulator fires. In both cases the regulators were completely dialled in when pressure was applied from the oxygen rack.

The member company provided its workforce with these recommendations to prevent recurrence:

  • Ensure the oxygen cylinders or banks are firmly secured.
  • Inspect the cylinder valve for oil, grease and damage to the valve handle. Do not use the cylinder if oil or grease or a damaged valve is found.
  • Momentarily open and close the cylinder valve prior to attaching the regulator. This dislodges any contaminants that are present and would otherwise enter the regulator.
  • Carefully inspect the regulator for oil, grease or damaged parts. Do not use a regulator with oil, grease contamination or broken parts.
  • Check that the regulator has the correct pressure rating and gas service for the cylinders being used.
  • Attach the regulator to the cylinder and secure tightly.
  • Stand so that the cylinder valve is between you and the regulator. Slowly and carefully, open the cylinder valve until the maximum pressure registers on the high pressure side. Then open the cylinder valve completely to seal the valve packing.
  • Adjust the low pressure side adjustment screw to the desired pressure and check the system for leaks.
  • When temporarily shutting down the system:
    • Secure the valve on the cylinder.
    • Open the valve on the downstream equipment – this will drain the system.
    • Close the valve on the downstream equipment and then turn the adjuster screw counter clockwise to release the pressure on the adjusting spring.
    • Check the gauges after a few minutes for verification that the cylinder valve is completely closed.

Latest Safety Flashes:

Crew transfer vessel (CTV) drifts onto turbine tower

A CTV drifted into and hit a nearby structure at 0.5 knots.

Read more
LTI: Fall from height during FRC maintenance

A worker fell 2.3 m to deck from a small boat in the davit, and broke a leg as a result. 

Read more
Near miss: narrowly avoided fall from height due to missing deck gratings

After a grating was removed, the Chief Engineer, on the way to inspect the work, nearly fell 4-5m.

Read more
MSF: A broken stretcher could have led to injury

The Marine Safety Forum (MSF) published Safety Alert 24-09 relating to a broken stretcher.

Read more
Positive story: Excellent galley hygiene and housekeeping

On a walk-around audit, a member highlights very high standards of housekeeping and hygiene in the galley on one of its vessels.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.