Fire in engine space on crew transfer vessel (CTV)

  • Safety Flash
  • Published on 30 June 2014
  • Generated on 21 November 2026
  • IMCA SF 10/14
  • 3 minute read

An incident has been bought to IMCA’s attention in which there was a small fire in the starboard engine space on a crew transfer vessel used in the offshore wind farm sector. 

What happened?

The incident occurred when on passage to an offshore wind farm. Shortly after leaving port, the fire alarm was activated in the starboard engine. Dark smoke was observed coming from the drain hole in the after inspection hatch of the starboard engine. On the CCTV into the engine space there was no indication of flames.

The starboard engine was shut down and full fire procedures were carried out. The COâ‚‚ system was also used, however on inspection after the incident it was found that the system had not deployed. Shore authorities were alerted and the vessel returned to port on one engine. All staff were safely landed ashore and the fire confirmed to be extinguished.

Investigation of the fire revealed the following:

  • Normal checks on the engines and inspection of the engine and jet spaces had been carried out before the voyage, and all was found to be in order.
  • The immediate cause of the fire was a rubber drain hose from a hatch combing catching fire as it was in contact with the exhaust system.
  • Although the drain pipe was heat resistant and the main engine exhaust was covered in thermal insulation, the drain pipe was badly positioned, crossing over the exhaust system.
  • The flames from the burning pipe were extinguished by oxygen starvation as a result of the shutdown of the engine fans and ventilators. The COâ‚‚ smothering system was not actually deployed.

The following actions were taken with regard to the fire:

  • Drain pipe on both engines replaced with a suitable thermally protected pipe which was run clear of any possible exposure to damage from the exhaust system.
  • A general focus on pipe inspections was produced and circulated.
  • Fire drills and specific vessel training to be updated to reflect lessons learnt from this incident.

Investigation of why the CO² system did not deploy revealed the following:

  • The valve to the engine space had not been opened.
  • The pin had not been removed from the valve head.
  • A brass lever had been forced in the wrong direction causing it to shear.
  • The instructions for the activation and effective use of the CO² system were not adequate to purpose.
  • They were located on the external surface of the drop down access door.
  • They are not readily visible to crew operating the system.
  • They did not highlight the need to remove the safety pin on the activation lever of the cylinder; The following actions were taken with regard to the failure to deploy the CO² smothering system.
  • Better and more detailed operating instructions issued to vessels with similar CO² smothering systems – including pictorial instructions for use.
  • Ensured that all crew members were fully conversant with the fixed fire fighting system fitted to the vessel and how to operate that fire fighting system.
Drain hole from which smoke was sighted

Drain hole from which smoke was sighted

Scorched drain pipe which was immediate cause of fire

Scorched drain pipe which was immediate cause of fire

The activation lever on the starboard cylinder was broken off, but the cylinder had not been activated

The activation lever on the starboard cylinder was broken off, but the cylinder had not been activated

Both selector valves to the port and starboard engine were in the closed position

Both selector valves to the port and starboard engine were in the closed position

Latest Safety Flashes:

LTI: serious finger injuries during crane operations

The boom of a 12 tonne crane moved towards the pipelay tower, and trapped the spotter’s left hand against a handrail. 

Read more
Finger injury caused during maintenance of rotating machinery

Although the electrical supply was isolated, a V-belt continued to rotate due to residual mechanical energy.

Read more
MSF: Serious hand injury (LTI) – failure to Isolate

Chief Engineer attempted to adjust an air filter housing clamp, and his hand entered the exposed hazard zone, contacting the rotating turbocharger fan.

Read more
MSF: Someone’s finger trapped in the door

The Marine Safety Forum (MSF) has published Safety Alert 26-15 relating to a finger caught in a door.

Read more
Hand injuries - keep your hands clear, every task, every time

One of our Members notes a spate of recent hand injuries occurring during multiple activities.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.