Unfamiliarity with DP system leads to an undesired event
- DP Event
- Published on 13 June 2019
- Generated on 26 December 2024
- DPE 02/19
- 2 minute read
Undesired event
Jump to:
Vessel specific familiarisation programmes and operation manuals should make allowances for crew members not being familiar with systems.
Comments
Both DPOs had several years’ experience but with a different DP control system where it is common to stop the vessel during a move by reducing speed to 0.0kts.
However, on the system fitted to this vessel a retardation factor is used so speed is reduced automatically when the stop request is made.
Setting a speed at 0.0kt led to an unstable situation. The master instructed DPOs to keep a minimum speed on DP of 0.1kts and not set speed to 0.0kts.
Considerations
- Vessel specific familiarisation programmes and operation manuals should capture and make allowance for crew members not being familiar with systems. Each system/vessel has peculiarities which must be taught and learned by the crew onboard.
- The DP system manufacturer should be involved as it should not be possible for the operator to apply a valid setting which then causes an unstable DP system.
- It is recognised practice to slow down during a move, but it is not considered good practice to use zero speed.
- The use of the present position would maintain the vessel in the wanted position.
Latest DP incidents
-
Prepare for 2025 solar activity
This case study covers events that occurred on the same vessel, eight months apart.
DPE 02/24
29 July 2024
Undesired event
-
Know your vessel capabilities and when to stop!
An incident that occurred on an equipment class 2 MODU, during well intervention operations.
DPE 02/24
29 July 2024
Incident
-
Duty/not duty, which is the question?
With no steering control of the port azimuth thruster, and no other thrusters operational, the heading of the FPU could not be maintained.
DPE 02/24
29 July 2024
Undesired event
-
You’ve got the ASOG, so now you’ve got to follow it
This case study examines an incident that occurred on an equipment class 2 MODU, during well intervention operations.
DPE 02/24
29 July 2024
Incident
-
Button trouble
A Dynamically Positioned vessel experienced a loss of Dynamic Positioning (DP) control while installing cable within a wind farm.
DPE 01/24
3 April 2024
Incident
The case studies and observations above have been compiled from information received by IMCA. All vessel, client, and operational data has been removed from the narrative to ensure anonymity. Case studies are not intended as guidance on the safe conduct of operations, but rather to assist vessel managers, DP operators, and technical crew.
IMCA makes every effort to ensure both the accuracy and reliability of the information, but it is not liable for any guidance and/or recommendation and/or statement herein contained.
Any queries should be directed to DP team at IMCA. Share your DP incidents with IMCA online. Sign-up to receive DP event bulletins straight to your email.